| 48mm x 48mm size |
| Products |
Typical functions |
| CB100 |
Standard temperature controller |
Communication, Large-size LED display |
| CB103 |
Standard temperature controller |
Analog retransmission output |
| SA100 |
Socket installation type temperature controller |
Socket installation |
| REX-D100 |
Standard temperature controller |
Universal input, Advanced fuzzy logic |
| REX-P24 |
Lamp/Soak temperature controller |
Program (two patterns), Timer control |
|
|
| CB100 Temperature Controller |

A catalog download is here.
CB_05E.pdf (227KB)
(CB series)
Specification files are in Adobe's Acrobat PDF file (version 4.0) format.
Acrobat Reader is required. |
| Input |
Thermocouple, RTD, DC voltage, DC current
* For DC current input, connect a 250W resister (sold separately) to the input terminals. |
| Sampling time |
0.5 sec. |
| Measuring accuracy |
Thermocouple
±(0.3% of reading + 1 digit) or ±2°C (4°F) whichever
is larger
RTD
±(0.3% of reading + 1 digit) or ±0.8°C (1.6°F) whichever
is larger
DC voltage and DC current
±(0.3% of span + 1 digit) |
| Out of an accuracy guarantee range |
Thermocouple R, S, B : 0 to 399°C |
| Control method |
PID control (with autotuning and self-tuning function)
* ON/OFF, P, PI and PD control are also selectable.
Heat/cool PID control (with autotuning) |
| Control output type |
Relay contact output
Voltage pulse output
DC current output : 4 to 20mA
Triac trigger output
Triac output |
| Communications |
RS-485 |
| External Dimensions |
48 x 48 x 100mm (W x H x D) |
| Standard function |
RUN/STOP switching |
| Optional function |
Alarm function : Up to 2 points (Temperature alarm, Loop break alarm)
Dustproof and waterproof protection : IP66 |
|
|
| Go to "Quick Reference Guide" Index Page. |
| Go to Page Top |
|
| CB103 Temperature Controller |

A catalog download is here.
CB3_03E.pdf (191KB)
(CB3 series)
Specification files are in Adobe's Acrobat PDF file (version 4.0)
format. Acrobat Reader is required. |
| Input |
Thermocouple, RTD, DC voltage, DC current
* For DC current input, connect a 250W resister (sold separately) to the input terminals. |
| Sampling time |
0.5 sec. |
| Measuring accuracy |
Thermocouple
±(0.3% of reading + 1 digit) or ±2°C (4°F) whichever
is larger
RTD
±(0.3% of reading + 1 digit) or ±0.8°C (1.6°F) whichever
is larger
DC voltage and DC current
±(0.3% of span + 1 digit) |
| Out of an accuracy guarantee range |
Thermocouple R, S, B : 0 to 399°C |
| Control method |
PID control (with autotuning and self-tuning function)
* ON/OFF, P, PI and PD control are also selectable. |
| Control output type |
Relay contact output
Voltage pulse output
DC current output : 4 to 20mA
Triac trigger output
Triac output |
| Communications |
None |
| External Dimensions |
48 x 48 x 100mm (W x H x D) |
| Standard function |
RUN/STOP switching |
| Optional function |
Alarm function : Up to 2 points (Temperature alarm, Loop break alarm)
Auxiliary output ( Alarm or RUN/STOP staus, Analog output )
Contact input : 1 point
Dustproof and waterproof protection : IP66 |
|
|
| Go to "Quick Reference Guide" Index Page. |
| Go to Page Top |
|
| SA100 Temperature Controller |

A catalog download is here.
SA100_01E.pdf (418KB)
Specification files are in Adobe's Acrobat PDF file (version 4.0)
format. Acrobat Reader is required. |
| Input |
Thermocouple, RTD, DC voltage, DC current
* For DC current input, connect a 250W resister (sold separately) to the input terminals. |
| Sampling time |
0.5 sec. |
| Measuring accuracy |
Thermocouple
±(1% of reading + 1 digit) or ±2°C (4°F) whichever
is larger
RTD
±(0.3% of reading + 1 digit) or ±0.8°C (1.6°F) whichever
is larger
DC voltage and DC current
±(0.3% of span + 1 digit) |
| Out of an accuracy guarantee range |
Thermocouple R, S, B : 0 to 399°C
Thermocouple T, U : Less than -100°C |
| Control method |
PID control (with autotuning and self-tuning function)
* ON/OFF, P, PI and PD control are also selectable.
Heat/cool PID control (with autotuning) |
| Control output type |
Relay contact output
Voltage pulse output
DC current output : 4 to 20mA |
| Communications |
RS-485 |
| External Dimensions |
48 x 48 x 70mm (W x H x D)
* Socket does not include it. |
| Standard function |
RUN/STOP switching |
| Optional function |
Alarm function : Up to 2 points (Temperature alarm, Loop break alarm)
Contact input : 2 points
Dustproof and waterproof protection : IP66 |
|
|
| Go to "Quick Reference Guide" Index Page. |
| Go to Top Page |
|
| REX-D100 Temperature Controller |

A catalog download is here.
D_01E.pdf (79.6KB)
(D series)
Specification files are in Adobe's Acrobat PDF file (version 4.0)
format. Acrobat Reader is required. |
| Input |
Universal input
Thermocouple, RTD, DC voltage, DC current
* For DC current input, connect a 250W resister (sold separately) to the input terminals. |
| Sampling time |
0.5 sec. |
| Measuring accuracy |
±(0.3% of spsn + 1 digit) |
| Cold junction temperature compensation error |
Within ±1.5°C (between 0 and 50°C) |
| Control method |
PID control (with autotuning and self-tuning function)
* ON/OFF, P, PI and PD control are also selectable.
Heat/cool PID control (with autotuning and self-tuning function) |
| Control output type |
Relay contact output
Voltage pulse output
DC current output
DC voltage output |
| Communications |
RS-485 |
| External Dimensions |
48 x 48 x 100mm (W x H x D) |
| Standard function |
Alarm function : Up to 2 points (Temperature alarm, Loop break alarm) |
| Optional function |
Heater break alarm (Single-phase, Three-phase)
Contact input
Analog output
Dustproof and waterproof protection : NEMA4X |
|
|
| Go to "Quick Reference Guide" Index Page. |
| Go to Page Top |
|
| REX-P24 Ramp/Sork Temperature Controller |

A catalog download is here.
P24_01E.pdf(61.4KB)
Specification files are in Adobe's Acrobat PDF file (version 4.0)
format. Acrobat Reader is required. |
| Storage program pattern |
Max. 2 patterns (8 segments per pattern) |
| Input |
Thermocouple, RTD |
| Sampling time |
0.5 sec. |
| Measuring accuracy |
±(0.3% of spsn + 1 digit) |
| Cold junction temperature compensation error |
Within ±1.5°C (between 0 and 50°C) |
| Control method |
PID control (with autotuning function)
* ON/OFF, P, PI and PD control are also selectable. |
| Control output type |
Relay contact output
Voltage pulse output
DC current output |
| Communications |
None |
| External Dimensions |
48 x 48 x 100mm (W x H x D) |
| Standard function |
Timer control |
| Optional function |
Level PID (4 level)
Contact output : Up to 2 points (Temperature alarm, Pattern end, Time signal,
Time-up)
Contact input : 2 points (STOP/START, RESET/RUN, RESET/START)
Dustproof and waterproof protection : NEMA4X |
|
|
| Go to "Quick Reference Guide" Index Page. |
| Go to Page Top |
|
 |
 |
RKC INSTRUMENT INC. |
|
|
|