| Accuracy ± (0.3% of span + 1digit) |
|
|
|
|
| REX-D100 temperature controller |

A catalog download is here.
D_01E.pdf (79.6KB)
(D series)
Specification files are in Adobe's Acrobat PDF file (version 4.0)
format. Acrobat Reader is required. |
| Input |
Universal input
Thermocouple, RTD, DC voltage, DC current
* For DC current input, connect a 250W resister (sold separately) to the input terminals. |
| Sampling time |
0.5 sec. |
| Measuring accuracy |
±(0.3% of spsn + 1 digit) |
| Cold junction temperature compensation error |
Within ±1.5°C (between 0 and 50°C) |
| Control method |
PID control (with autotuning and self-tuning function)
* ON/OFF, P, PI and PD control are also selectable.
Heat/cool PID control (with autotuning and self-tuning function) |
| Control output type |
Relay contact output
Voltage pulse output
DC current output
DC voltage output |
| Communications |
RS-485 |
| External Dimensions |
48 x 48 x 100mm@(W x H x D) |
| Standard function |
Alarm function : Up to 2 points (Temperature alarm, Loop break alarm) |
| Optional function |
Heater break alarm (Single-phase, Three-phase)
Contact input
Analog output
Dustproof and waterproof protection : NEMA4X |
|
|
| Go to "Quick Reference Guide" Index Page. |
|
| Go to Page Top |
|
| REX-D400 temperature controller |

A catalog download is here.
D_01E.pdf (79.6KB)
(D series)
Specification files are in Adobe's Acrobat PDF file (version 4.0)
format. Acrobat Reader is required. |
| Input |
Universal input
Thermocouple, RTD, DC voltage, DC current
* For DC current input, connect a 250W resister (sold separately) to the input terminals. |
| Sampling time |
0.5 sec |
| Measuring accuracy |
±(0.3% of spsn + 1 digit) |
| Out of an accuracy guarantee range |
Thermocouple B : Less than 400°C |
| Cold junction temperature compensation error |
Within ±1.5°C (between 0 and 50°C) |
| Control method |
PID control (with autotuning and self-tuning function)
* ON/OFF, P, PI and PD control are also selectable.
Heat/cool PID control (with autotuning and self-tuning function) |
| Control output type |
Universal output (OUT1)
Relay contact output
Voltage pulse output
DC current output
DC voltage output |
| Communications |
RS-485
RS-422A |
| External Dimensions |
48 x 96 x 100mm (W x H x D) |
| Standard function |
Alarm function : Up to 2 points (Temperature alarm, Loop break alarm) |
| Optional function |
Heater break alarm (Single-phase, Three-phase)
Contact input
Analog output |
|
| Go to "Quick Reference Guide" Index Page. |
|
|
| Go to Page Top |
|
| REX-D900 temperature controller |

A catalog download is here.
D_01E.pdf (79.6KB)
(D series)
Specification files are in Adobe's Acrobat PDF file (version 4.0)
format. Acrobat Reader is required. |
| Input |
Universal input
Thermocouple, RTD, DC voltage, DC current
* For DC current input, connect a 250W resister (sold separately) to the input terminals. |
| Sampling time |
0.5 sec. |
| Measuring accuracy |
±(0.3% of spsn + 1 digit) |
| Out of an accuracy guarantee range |
Thermocouple B : Less than 400°C |
| Cold junction temperature compensation error |
Within ±1.5°C ( between 0 and 50°C ) |
| Control method |
PID control (with autotuning and self-tuning function)
* ON/OFF, P, PI and PD control are also selectable.
Heat/cool PID control (with autotuning and self-tuning function) |
| Control output type |
Universal output (OUT1)
Relay contact output
Voltage pulse output
DC current output
DC voltage output |
| Communications |
RS-485
RS-422A |
| External Dimensions |
96 x 96 x 100mm (W x H x D) |
| Standard function |
Alarm function : Up to 2 points (Temperature alarm, Loop break alarm) |
| Optional function |
Heater break alarm (Single-phase, Three-phase)
Contact input
Analog output |
|
|
| Go to "Quick Reference Guide" Index Page. |
|
| Go to Page Top |
 |
 |