| Storage program pattern |
Max. 2 patterns
8 segments per pattern
(Max. 16 segments when linking 2 patterns of 8 segments each.) |
| Input |
Thermocouple, RTD |
| Sampling time |
0.5 sec. |
| Measuring accuracy |
±(0.3% of spsn + 1 digit) |
| Out of an accuracy guarantee range |
Thermocouple B : Between 0 and 400°C |
| Cold junction temperature compensation error |
±1.5°C (between 0 to 50°C) |
| Control method |
PID control ( with autotuning )
* ON/OFF, P, PI and PD control are also selectable.
Heat/cool PID control ( with autotuning ) |
| Control output type |
Relay contact output
Voltage pulse output
DC current output |
| Communications |
Not supplied |
| External Dimensions |
96 x 96 x 100mm ( W x H x D ) |
| Standard function |
Programmable ramp/sork control |
| Optional function |
Level PID control (4 level)
Alarm function : Max. 2 points (Temprature alarm)
Pattern end output : 1 point
Time signal output : 1 point
External contact input : 4 points
(RESET, RUN, HOLD, STEP)
Retransmission output : 1 point |