| Storage program pattern |
Max. 16 patterns
16 segments per pattern
( Max. 256 segments when linking 16 patterns of 16 segments each. ) |
| Input |
Thermocouple, RTD, DC voltage, DC current |
| Sampling time |
0.5 sec. |
| Measuring accuracy |
Thermocouple :
±(0.3% of reading + 1 digit) or ±2°C
RTD
±(0.3% of reading + 1 digit) or ±0.8°C
DC voltage and DC current
±(0.2% of span + 1 digit) |
| Out of an accuracy guarantee range |
Thermocouple R, S, B : Between 0 and 400°C |
| Control method |
PID control ( with autotuning )
* ON/OFF, P, PI and PD control are also selectable.
Position proportioning control |
| Control output type |
Relay contact output
Voltage pulse output
DC current output
DC voltage output
Triac trigger output |
| Communications |
RS-232C
RS-422A |
| External Dimensions |
96 x 96 x 150mm ( W x H x D ) |
| Standard function |
Programmable ramp/sork control
Multi memory area : 8 areas
Pattern end output : 1 point ( Open collector )
Time signal output : 4 points ( Open collector )
External contact input : 9 points
( RESET, RUN, HOLD, STEP, Pattern SET )
FAIL alarm |
| Optional function |
Alarm function : Up to 2 points (Temperature alarm, Heater break alarm)
Analog retransmission output |