Compliance
 |
RoHS compliant |
|
 |
CE Marking |
|
 |
UL, cUL |
|
 |
C-Tick Mark |
|
 |
Reinforced insulation |
Specifications
| Input |
| a) |
Temperature input group |
|
|
Thermocouple : K, J, E, T, R, S, B, N (JIS/IEC), PLII (NBS), W5Re/W26Re
(ASTM) |
|
|
RTD : Pt100 (JIS/IEC), JPt100 (JIS) · 3-wire system |
| b) |
Voltage/Current input group |
|
|
Voltage input (Input impedance : Approx. 1MW) |
|
|
|
0 to 1V DC, 0 to 5V DC, 1 to 5V DC, 0 to 10V DC |
|
|
Current input (Input impedance : 250W) |
|
|
|
4 to 20mA DC, 0 to 20mA DC |
| * |
For current input, connect is a 250W shunt resistor to the input terminals. Model code : KD100-55 |
| * |
Inputs is selectable within each group. |
|
| Sampling time |
0.25 sec |
| Measuring accuracy |
| Input Type |
Range |
Accuracy |
| K, J, T, E *1 |
Lower than -100°C(-148°F) |
±(2.0°C[3.6°F] + 1digit) |
|
-100 to 500°C(-148 to 932°F) |
±(1.0°C[1.8°F] + 1digit) |
| 500°C(932°F) or higher |
±(0.2% of Reading + 1digit) |
N, R, S, PLII *2
W5Re/W26Re |
Lower than 0°C(-32°F) |
±(4.0°C[7.2°F] + 1digit) |
| 0 to 1000°C(32 to 1832°F) |
±(2.0°C[3.6°F] + 1digit) |
| 1000°C(1832°F) or higher |
±(0.2% of Reading + 1digit) |
| B |
Lower than 400°C(752°F) |
±(70°C[126°F] + 1digit) |
| 400 to 1000°C(752 to 1832°F) |
±(2°C[3.6°F] + 1digit) |
| 1000°C(1832°F) or higher |
±(0.2% of Reading + 1digit) |
| Pt100, JPt100 |
Lower than 200°C(752°F) |
±(0.4°C[0.7°F] + 1digit) |
| 200°C(392°F) or higher |
±(0.2% of Reading + 1digit) |
| Voltage/Current |
-span to +span |
±(0.2% of span + 1digit) |
| *1: |
Accuracy is not guaranteed for less than -100°C(-148°F) |
| *2: |
Accuracy is not guaranteed for less than 400°C(752°F) for input type R, S, B and W5Re/W26Re. |
|
| Influence of ambient temperature |
a) Temperature input : ±0.06°C/°C [at 5 to 40°C]
b) Voltage/Current input group : ±0.06% of span/°C [at 5 to
40°C] |
| Close horizontal mounting error |
±2°C(3.6°F) [Less than -100°C(-146°F) input :±3.5°C(6.3°F)] |
| Control method |
| a) |
PID control with autotuning |
|
|
P, PI, PD, ON/OFF control selectable Direct action/Reverse action is selectable |
| b) |
Heat/Cool type PID control with autotuning |
|
| Control output |
Relay contact output, Form a contact, 250V AC 3A (Resistive load)
Voltage pulse output, 0/12V DC
Current output 4 to 20mA DC, 0 to 20mA DC
Voltage output, 0 to 5V DC, 1 to 5V DC, 0 to 10V DC
SSR (Triac) output Rated current : 0.5A
Open collector output (Sink type) |
Communication
(Optional) |
RS-485 (ANSI X3.28 sub-category 2.5A4[RKC standard], MODBUS-RTU) |
| Standard function |
PV bias
Digital filter
Ramp-to-setpoinst
SV step function : Number of SV : 4 points (Default : 1 points)
Timer function
Loader communication (Communication converter COM-K and software WinUCI
for RB series and a Windows XP PC are necessary)
Easy Fine tuning with 6-level of control response adjustment |
| Optional function |
Event (Alarm) function : Up to 4 poinsts
Control loop break alarm (LBA)
Heater break alarm (HBA)
Analog retransmission output
Digital input : 2points |
Dimensions
* If you specified the waterproof and dustproof structure, four mounting
brackets are included with the RB900 as accessories.
* Case rubber packing (optional) [Waterproof/dustproof] |
(Unit : mm) |
 |
 |
 |
< Close horizontal mounting > Up to 6 units |
 |
| Waterproof/dustproof is not available for close horizontal mounting. |
|
Model codes
*1
*2
*3 |
When control method is selected for PID control (Code : F, D), output 2
is available for analog retransmissin output.
On the RB100, the event 3 output function can be specified for output 2.
The number of DO points is limited in some combinations of OUT1 and OUT2
(control output) types. |
| Maximum number of digital outputs (DO) by combinations of output (OUT1
and OUT2) |
 |
: Represents selection of digital outputs DO3 and DO4 are not available. |
| *1 |
When the instrument has two digital outputs (DO1 and DO2) and no OUT2 output,
"V" type output (load: 40mA) can be specified for OUT1. |
Input range code
| Inputs is selectable within each group. |
Temperature Input Group (Field-programmable)
DC Current, Voltage Group (Field-programmable)
Output code
Output 1 Code Table
Output 2 Code Table

Quick start code
Quick start code tells the factory to ship with each parameter preset to the values detailed as specified by the customer.
Quick start code is not necessarily specified when ordering, unless the preset is requested.
These parameters are software selectable items and can be re-programmed in the field via the manual. |

|